Pneumatic valve positioner YT 1200 series of products from the control system
receives the air pressure is 3 ~ 15 psi signal, according to the signal pressure precision
adjustment device of the valve opening.
Second, Technical Data
Model | YT1200L | YT1200R | ||
Project | Straight travel | Angular travel | ||
Single-acting | Double-acting | Single-acting | Double-acting | |
Input signal | 0.2~1.0kgf/cm2(3~15psi), (Are also applicable to the process and control) | |||
Trip | Standard:20~70mm Selection:70~150mm | 0~90° | ||
Air supply interface size | Standard:PT1/4(Pressure gauge PT/1/8) Selection:NPT1/4(Pressure gauge NPT/1/8) | |||
Pressure gauge (output pressure) | Standard: 0~2.0kgf/cm2 0~4.0kgf/cm2 0~10kgf/cm2 | Standard: 0~2.0kgf/cm2 0~4.0kgf/cm2 0~10kgf/cm2 | ||
Supply pressure | 1.4~7.0kgf/cm2(20~100psi) | |||
Protection grade | IP66 | |||
Cam | Linear | |||
Environment temperature | -20~70℃ | |||
Linear | ±1.0% F·S | ±2.0% F·S | ||
Degree of lag | ±0.75% F·S | ±1.0% F·S | ||
Sensitivity | ±0.3% F·S | ±0.5% F·S | ||
Repetitive | ±0.3% F·S | ±0.5% F·S | ||
Air consumption | 3.0LPM(Sup=1.4kgf/cm2), 11LPM(Sup=4.0kgf/cm2) | |||
Flow | 80LPM(Sup=1.4kgf/cm2),200LPM(Sup=4.0kgf/cm2) | |||
Material | Die casting aluminum | |||
Weight | 1.7kg | |||
*
The above parameters is in ambient temperature 20℃, absolute pressure
760mmHg, 65% relative humidity environment, test the value of the
standard according to my company.
Third, Model Specification
YT-1000 0 0 0 0 0 0
Model | Action type | Action way | Feedback pole (YT-1200L) | Feedback pole (YT-1200R) | Air Supply interface | Environment temperature |
YT1200 | L Linear | S Single acting | 1 40mm (Following) | 1 M6 X 40L | 1 PT | S -20℃~70℃ |
R Angular travel | D Double acting | 2 40~70mm | 2 M6 X 63L | 2 NPT | H -20℃~120℃ | |
3 70~100mm | 3 M8 X 40L | L -40℃~70℃ | ||||
4 100~130mm | 4 M8 X 63L | |||||
5 130~150mm | 5 NAMUR (Standard) |
* Special type products, please contact our company or our company agent.